Two separate sizes: the battery in kWh sets how long; the inverter in kW sets how much at once.
Usable capacity: not every kWh on the label can be used. LFP batteries let you use about 90% or more.
Round trip: about 90% of what goes into a battery comes back out.
Surge: motors (refrigerators, well pumps, compressors) pull several times their running watts for a moment at start-up, so the inverter's surge rating has to cover the biggest one.
C-rate: discharge power ÷ battery size. A 15 kWh battery giving 7.5 kW is at 0.5C.
Worked example
Critical loads use 6 kWh a day. You want 2 days with no sun. With an inverter at 92% and 90% usable capacity: battery = 6 × 2 ÷ (0.92 × 0.90) = about 14.5 kWh on the label.
Problems
A refrigerator runs at 150 W for about 8 hours a day and starts at about 1,000 W. Lights total 200 W for 5 hours. Wi-Fi uses 15 W all day. What is the daily kWh?
For the same loads, what's the smallest inverter that will start the refrigerator while the lights are on?
How big a battery covers those loads for 3 sunless days at 92% inverter efficiency and 90% usable?
Stretch: after an outage the 14.5 kWh battery is empty. A sunny day makes 33 kWh while loads use 6 kWh; a cloudy day makes 9 kWh. Allowing about 5% loss in charging, how long does each kind of day take to refill the usable 13 kWh?
A pavilion battery holds 15 kWh and the car charger pulls 7.2 kW. What C-rate is that, and why does it matter?
On the pavilion
Use the battery percentage before and after a known load (a kettle, a heater) runs for 30 minutes to measure the battery's real usable size.
Fridge 1.2 + lights 1.0 + Wi-Fi 0.36 = about 2.6 kWh a day.
Answer
About 1,000 + 200 + 15 = 1,215 W of surge. Choose an inverter rated well above that for continuous power and with a surge rating comfortably over it.
Answer
2.6 × 3 ÷ (0.92 × 0.90) = about 9.4 kWh.
Answer
About 13.7 kWh has to go in. Sunny: 27 kWh is spare, so about half a sunny day. Cloudy: only 3 kWh is spare, so four to five cloudy days. That gap is why the next storm after a cloudy week is the real test.
Answer
7.2 ÷ 15 = about 0.5C. Higher C-rates heat the battery and wear it faster, and every battery has a maximum.