Wires, code and safety

Voltage drop, wire size, series strings in the cold, the electrical code, and why a licensed electrician does the work.

UPPER SCHOOL · MODULE 4 OF 8

The ideas

Worked example

A 120-volt circuit runs 100 feet to outlets drawing 12 amps. On 12 gauge: 2 × 100 × 12 × 1.93 ÷ 1,000 = 4.6 volts, 3.9% of 120, which is too much. On 10 gauge: 2.9 volts, 2.4%. Use 10 gauge.

Problems

  1. A 240-volt car charger draws 32 amps through 60 feet of 8 gauge wire. What's the voltage drop in volts and percent?
  2. A panel's open-circuit voltage is 49 V and rises about 10% on the coldest morning. The inverter's maximum input is 600 V. How many panels fit in one string?
  3. Why does a 15-amp breaker go with 14 gauge wire and not 12 gauge with a 30-amp breaker?
  4. Name two reasons students don't open the equipment cabinet.

On the pavilion

With the electrician, trace the path of power from the panels to the outlets and draw it as a one-line diagram. Label every disconnect.

Read it on this site

Questions people ask

Answer

2 × 60 × 32 × 0.764 ÷ 1,000 = about 2.9 volts, 1.2% of 240.

Answer

49 × 1.10 = 53.9 V per panel. 600 ÷ 53.9 = 11.1, so 11 panels.

Answer

The breaker protects the wire. It has to trip before the wire carries more current than it can handle without overheating.

Answer

Stored battery energy and panel DC are live even when switches are off, and DC arcs are hard to stop. The code requires the work be done by a qualified person.