The NEC 680 distances that decide where posts, fans, lights, outlets and solar racking can go on a pool house. Section numbers are from the 2017 NEC, which North Carolina enforces on houses.
| Item | Rule | 2017 NEC |
|---|---|---|
| Perimeter bonding | Extends at least 3 feet from the inside walls of the pool | 680.26(B)(2) |
| Fixed metal parts | Bonded unless more than 5 feet horizontally from the inside walls, more than 12 feet above the water, or behind a permanent barrier | 680.26(B)(7) |
| Lights, lighting outlets, ceiling fans | Over the pool or within 5 feet horizontally: generally 12 feet above maximum water level; GFCI rules for the 5-to-10-foot zone | 680.22(B) |
| Pump-motor receptacles | At least 6 feet from the inside walls | 680.22(A)(2) |
| Required general receptacle | At least one GFCI receptacle between 6 and 20 feet from the water | 680.22(A)(1) |
| Receptacles within 20 feet | 15- and 20-amp, 125-volt: GFCI protected | 680.22(A)(4) |
| Pump motors | GFCI on single-phase 120- to 240-volt pump-motor outlets, hardwired or plugged in | 680.21(C) |
| Equipment disconnect | Readily accessible, within sight, generally at least 5 feet from the inside walls | 680.13 |
| Overhead wiring | Clearances over and near the pool | 680.9 |
| Underground wiring | Location limits near the pool | 680.11 |
| Feeders to pool equipment | Feeder rules for pool panels | 680.25 |
Under 2017 NEC 680.26(B)(7), fixed metal parts must be bonded unless they are more than 5 feet horizontally from the inside walls of the pool, more than 12 feet above the maximum water level, or separated by a permanent barrier. The perimeter bonding extends at least 3 feet from the inside walls.
Under 2017 NEC 680.22(B), new outdoor lights, lighting outlets and ceiling-suspended fans over the pool or within 5 feet horizontally of its inside walls generally need 12 feet of clearance above the maximum water level, with specific exceptions.
Pool pump-motor receptacles must be at least 6 feet from the inside walls (680.22(A)(2)). Every 15- or 20-amp, 125-volt receptacle within 20 feet must be GFCI protected, and at least one GFCI receptacle is required between 6 and 20 feet from the water.
If the racking or the frame's steel connectors fall within 5 feet horizontally of the inside pool wall and no exception applies, they generally get bonded to the pool's equipotential bonding. The PV equipment ground doesn't replace that bonding, and the bonding doesn't replace the equipment ground.
Under 2017 NEC 680.13: readily accessible, within sight of the equipment it serves, and generally at least 5 feet horizontally from the inside walls of the pool unless a permanent barrier separates them.
Pool notes in the field guide · Which code applies in NC
Generator Envy provides the structure and the stamped structural drawings. Wire sizes, breakers, branch circuits, the point of connection and all electrical work are designed and installed by a licensed electrician under a local permit. Code notes here are pointers to check, not legal or engineering advice; your inspector has the final say.
How the Duke Energy PowerPair rebate is figured: $0.36 per AC watt up to 10 kW AC plus $400 per kWh of battery up to 13.5 kWh, $9,000 max.
Read it →
What size generator do I need, and how long will a battery run the house? Pick what you want running and for how long, and this free calculator gives
Read it →
Trucks that can power your home: Scout Traveler and Terra, Ram 1500 REV, Tesla Cybertruck, Silverado EV, Sierra EV and Hummer EV, Rivian R2 and R1, an
Read it →
Have a question we did not answer? Write to stan@generatorenvy.com. Stan grumbles, but a real person answers.